As per ___ guidelines, if the ratio of carbon dioxide (CO₂) and carbon monoxide (CO) in dissolved gas analysis is ___, it is predicted that the condition of paper insulation inside the transformer is poor.
There is one IEC guideline, number is IEC 599, Statement of guideline is that "If the ratio of carbon dioxide and Carbon monoxide in Dissolve gas analysis test result is more than 11, it is predict that the condition of paper insulation inside the transformer is poor." For healthy condition this ratio will be between 4 to 11.
The magnitude of earth fault current for a given fault position within a winding demands upon the winding connections and method of neutral grounding. Earth fault protection for an electric motor is provide by instantaneous relay having a setting of approximately 30% of motor rated current in the residual circuits of two CTs and with ground wire.
In FDLF method, B' corresponds to susceptance of unknown of PQ and PV bus Order of B' matrix is = (n -1)*(n - 1) Where n is total no. of buses. Order of B'' = (n - m - 1)*(n - m - 1)
Bus Type - Known Parameter - Unknown Parameter Load Bus -P, Q - V, phase angle Generator Bus - P, V (magnitude) - Q, Voltage phase angle Slack Bus Voltage - magnitude and phase angle - P, Q