A 200/400 V, 20 kVA, 2-winding transformer is connected as an auto-transformer to transform 600 V to 200 V. Calculate the kVA rating of the auto-transformer.

50 kVA
25 kVA
60 kVA
30 kVA

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 3)
Determine the ohmic value of the current limiting reactor per phase external to a 40 MVA, 15 kV, 50 Hz, three phase synchronous generator which can limit the current on short circuit of 6 times the full load current. The reactance of the synchronous generator is 0.06 pu.

0.4 Ω
0.6 Ω
0.2 Ω
0.8 Ω

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 3)
In a single phase energy meter, the pressure / voltage coil is wound on

the centre limb of the laminated core / the middle limb of the shunt magnet
both the limbs of the laminated core with same turns
the edges of the limb on the laminated core
both the limbs of the laminated core with different turns

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 3)
In which of the following situations, there is no need to provide directional overcurrent protection.

double end fed, single feeder
ring main
single end fed, single feeder
single end fed, parallel feeder

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP