MGVCL Exam Paper (30-07-2021 Shift 3)
A 200/400 V, 20 kVA, 2-winding transformer is connected as an auto-transformer to transform 600 V to 200 V. Calculate the kVA rating of the auto-transformer.
Here auto transformer change voltage from 600 V to 200 V. Voltage ratio (a) = 600/200 = 3 kVA rating of the auto-transformer = (a/(a - 1))*(kVA rating of auto transformer) = (3/2)*20 = 30 kVA
The tendency of a Reach of Distance Relay to operate at impedance larger than its setting value is known as overreach. Overreach is the presence of d.c. offset in the fault current wave, as the offset current has a higher peak value than that of a symmetrical wave for which the relay is set.
Bus Type - Known Parameter - Unknown Parameter Load Bus -P, Q - V, phase angle Generator Bus - P, V (magnitude) - Q, Voltage phase angle Slack Bus Voltage - magnitude and phase angle - P, Q