MGVCL Exam Paper (30-07-2021 Shift 3)
Murray loop test is performed on a faulty cable 300 m long. At balance, the resistance connected to the faulty core was set at 20 Ω and the resistance of the resistor connected to the sound core was 40 Ω. Calculate the distance of the fault point from the test end.

400 m
100 m
300 m
200 m

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 3)
In which of the following situations, there is no need to provide directional overcurrent protection.

ring main
single end fed, parallel feeder
single end fed, single feeder
double end fed, single feeder

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 3)
The DC offset in fault current causes conventional over-current (OC) relays to :

sometimes under-reach and sometimes over-reach
under-reach
over-reach
reach remains unaffected due to DC offset

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP