Bus Type - Known Parameter - Unknown Parameter Load Bus -P, Q - V, phase angle Generator Bus - P, V (magnitude) - Q, Voltage phase angle Slack Bus Voltage - magnitude and phase angle - P, Q
Frequency response analysis is the technique whereby a sinusoidal test signal is used to measure points on the frequency response of a transfer function or impedance function. Sweep Frequency Response Analysis (SFRA) testing provides insight into the mechanical and electrical integrity of transformers.
Main Purpose of SFRA Test: Transformer Core displacement Winding displacement for both rotor and transformer Broken or loosen clamp connections Inter turn short circuit Internal short circuit Winding to Core Earth fault Winding Open circuit condition
Short circuit current is the current passing through a solar cell when voltage is zero across the solar cell, which happens when a solar cell is short circuited. Usually it is denoted Isc. solar cell have short-circuit currents between about 28 mA/cm² and 35 mA/cm²
Type B MCB: Type B devices are generally suitable for domestic applications. They are designed to trip at fault currents of 3 - 5 times rated current.
Type C MCB: Type C devices are the normal choice for commercial and industrial applications These devices are designed to trip at 5 - 10 times rated current
Type D MCB: The Type D devices have more limited applications, normally in industrial use where high inrush currents may be expected. Type D devices are designed to trip at 10 - 20 times.
Value of power factor is varies from 0 to 1. R→PF = 1 L→PF = 0 lag C→PF = 0 lead R-L→0 lag < PF < 1 R-C→0 lead < PF < 1 R-C-L→depends on value of R, L and C. PF = R/Z