A 1000 kVA ONAN cooled transformer has a load of 500 kVA throughout the day except for a period of 4 hours. What is the permissible overload for a duration of four hours. Assume the permissible load kVA as a fraction of rated kVA is 1.24.
Class B trip curve : The MCB with class B trip characteristics trips instantaneously when the current flowing through it reaches between 3 to 5 times rated current. These MCBs are suitable for cable protection.
Class C trip curve: MCB with class C trip characteristics trips instantaneously when the current flowing through it reaches between 5 to 10 times the rated current. Suitable Domestic and residential applications and electromagnetic starting loads with medium starting currents.
Class D trip curve: MCB with class D trip characteristics trips instantaneously when the current flowing through it reaches between Above 10 (excluding 10) to 20 times the rated current. Suitable for inductive and motor loads with high starting currents.
Class K trip curve: MCB with class K trip characteristics trips instantaneously when the current flowing through it reaches between 8 to 12 times the rated current. Suitable for inductive and motor loads with high inrush currents.
Simple logic of reactance diagram is that simplified equivalent circuit of power system in which the various components of power system are represented by their reactances. The reactance diagram can be obtained from impedance diagram if all the resistive components are neglected.
Equivalent resistance of the circuit, Req = (12||18) + 8 Req = 7.2 + 8 Req = 15.2 ohm Source current = current through 8 ohm resistor, I = Vr/R8 I = 20/8 I = 2.5 A Supply votage V = I*Req V = 2.5*15.2 V = 38 V