A 1000 kVA ONAN cooled transformer has a load of 500 kVA throughout the day except for a period of 4 hours. What is the permissible overload for a duration of four hours. Assume the permissible load kVA as a fraction of rated kVA is 1.24.
In single phase energy meter, Current coil is made up from thick wire having few no. of turns. Pressure coil is made up from thin wire having more no. of turns.
The neutral point of a generator is usually earthed to facilitate protection of the stator winding and associated system. Earthing also prevents damaging transient overvoltages in the event of an arcing earth fault or ferro resonance. For HV generators, impedance is usually inserted in the stator earthing connection to limit the magnitude of earth fault current.