The line currents in amperes in phases a, b and c respectively are 500 +j150, 100 – j600 and – 300 + j600 referred to the same reference vector with phase sequence of abc. Find the symmetrical component of currents.
Ia₀ = (100+j50) AIa₁ = (546.41+j165.47) AIa₂ = (-146.41-j65.47) A
A term brown out means it is an intentional or unintentional drop in voltage in an electrical power supply system. Brown outs are long-term (hours-long) voltage sags caused by system overload. Deviations from the regular sinusoidal wave, both on the utility side and on the customer side, result in poor power quality.
MCCB stands for Moulded Case Circuit Breaker. MCB stands for Miniature Circuit Breaker. ELCB stands for Earth Leakage Circuit Breaker RCCB stands for Residual Current Circuit Breaker.