MGVCL Exam Paper (30-07-2021 Shift 1)
Which among the following are included in the two part tariff? i. Fixed charges ii. Running charges iii. Semi fixed charges
Two-part tariff: In this type of tariff, the total bill is divided into two parts. The first one is the fixed charge and the second is the running charge. The fixed charge is because of the maximum demand and the second charge depends on the energy consumption by the load.
The magnitude of earth fault current for a given fault position within a winding demands upon the winding connections and method of neutral grounding. Earth fault protection for an electric motor is provide by instantaneous relay having a setting of approximately 30% of motor rated current in the residual circuits of two CTs and with ground wire.
The connection of CT on primary and secondary side is always reverse to the connection of transformer. To protect the power transformer with star-delta against fault, the type of connection of CTs should be in the delta–star connection otherwise the relay will operate when an external fault occurs due to zero sequence currents
Bus Type - Known Parameter - Unknown Parameter Load Bus -P, Q - V, phase angle Generator Bus - P, V (magnitude) - Q, Voltage phase angle Slack Bus Voltage - magnitude and phase angle - P, Q