Murray loop test is performed on a faulty cable 300 m long. At balance, the resistance connected to the faulty core was set at 15 Ω and the resistance of the resistor connected to the sound core was 45 Ω. Calculate the distance of the fault point from the test end.
A form of AC testing that applies voltage and measures the leakage/loss current of electrical insulation. It is a type of insulation testing used to evaluate the integrity of electrical insulation.
In DC microgrid system, Efficiency α 1/Pin For 1 kW loss injecting power is 20 kW For 1.5 kW loss injecting power will be proportional to 30 kW So, Efficiency will be reduced 0.025