Murray loop test is performed on a faulty cable 300 m long. At balance, the resistance connected to the faulty core was set at 15 Ω and the resistance of the resistor connected to the sound core was 45 Ω. Calculate the distance of the fault point from the test end.

75 m
225 m
150 m
450 m

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 1)
The normal percentage bias setting of differential relay used for transformer protection will be

between 50% and 75%
below 10%
between 10% and 50%
above 75%