Murray loop test is performed on a faulty cable 300 m long. At balance, the resistance connected to the faulty core was set at 15 Ω and the resistance of the resistor connected to the sound core was 45 Ω. Calculate the distance of the fault point from the test end.
For lagging power factor = (IR*cosφ + Ixsinφ)/Vr For leading power factor = (IR*cosφ - Ixsinφ)/Vr Zero voltage regulation occurs on leading power factor only.
For small turbine starts generating power 12.6 kph (3.5 m/s) is the typical cut-in speed. At 36–54 kph (10–15 m/s) produces maximum generation power. At 90 kph (25 m/s) maximum, the turbine is stopped or braked.
For M no. of series configuration of solar cell, Open circuit voltage of PV module= M*Voc = 20*0.7 = 14 V Short circuit current of PV module = M*Isc = 20*4 = 80 A