In bias differential protection for transformer, There are two basic settings required to setup the percentage biased differential protection. 1. Minimum pickup 2. The slope.
The minimum pick-up covers the transformer magnetizing current typically 1-4% of transformer rating. A pick up of 0.2 to 0.3 times the TAP is recommended for general cases.
The slope is defined by determining the potential sources of differential current.
As per the key statistics data of IEA With electricity consumption reached to 1,164 TWh in the country till November 2019, India ranked third among the top ten electricity consuming countries across the globe.
For M no. of series configuration of solar cell, Open circuit voltage of PV module= M*Voc = 20*0.7 = 14 V Short circuit current of PV module = M*Isc = 20*4 = 80 A
The series electromagnet is energized by a coil known as current coil which is connected in series with the load so that it carry the load current. The flux produced by this magnet is proportional to and in phase with the load current.