Intern turn winding fault can be easily detect by differential protection relay. Also detect by buchholz relay (gas operated relay), cause buchholz relay is used to detect the internal fault of transformer.
The methods often employed in practice to improve system stability are: 1. Increasing System Voltage 2. Reduction in Transfer Reactance 3. Using High Speed Circuit Breaker 4. Automatic Reclosing 5. Transient Stability 6. Turbine Fast Valving 7. Application of Braking Resistors 8. Single Pole Switching:
The ratio of full load current to short circuit current = 1/5 Xsc = j/(1/5) External reactance required = j*((1/5) - 0.05)) = j*0.15 pu Full load current = (30*1000)/(√3*11) = 1574.6 A Per unit reactance = j*0.15 = (I*Xr)/V j*0.15 = (1574.6*Xb)/((11/√3)*1000)) = 0.60 ohm
Voltage sag: It is usually associated with system faults but can also be caused by energization of heavy loads or starting of large motors. Voltage sag is the short reduction in the RMS voltage between 0.1 to 0.9 pu for a duration of 0.5 cycle to 1 minute
In FDLF method, B' corresponds to susceptance of unknown of PQ and PV bus Order of B' matrix is = (n -1)*(n - 1) Where n is total no. of buses. Order of B'' = (n - m - 1)*(n - m - 1)
The series electromagnet is energized by a coil known as current coil which is connected in series with the load so that it carry the load current. The flux produced by this magnet is proportional to and in phase with the load current.