The operating time of an inverse definite minimum time (IDMT) overcurrent relay corresponding to plug-setting multiplier (PSM) = 1 and time-multiplier setting (TMS) = 1 will be
A grid-interactive photovoltaic (PV) system uses solar energy to generate renewable power that charges batteries for use during power failures and feeds power into the electricity grid. Grid-interactive systems are based on their grid-tied and off-grid counterparts.
The ratio of full load current to short circuit current = 1/5 Xsc = j/(1/5) External reactance required = j*((1/5) - 0.05)) = j*0.15 pu Full load current = (30*1000)/(√3*11) = 1574.6 A Per unit reactance = j*0.15 = (I*Xr)/V j*0.15 = (1574.6*Xb)/((11/√3)*1000)) = 0.60 ohm