Let, E→EMF in volt φ→Flux in weber A→Parallel path (for wave winding = 2) Z→No. of armature conductors N→speed in rpm P = Number of poles E = PφNZ/(60A) E = 8*0.020*625/(60*2) E = 500 V
The ratio of full load current to short circuit current = 1/5 Xsc = j/(1/5) External reactance required = j*((1/5) - 0.05)) = j*0.15 pu Full load current = (30*1000)/(√3*11) = 1574.6 A Per unit reactance = j*0.15 = (I*Xr)/V j*0.15 = (1574.6*Xb)/((11/√3)*1000)) = 0.60 ohm
In DC microgrid system, Efficiency α 1/Pin For 1 kW loss injecting power is 20 kW For 1.5 kW loss injecting power will be proportional to 30 kW So, Efficiency will be reduced 0.025