A single phase motor connected to 400 V, 50 Hz supply takes 30 A at a power factor of 0.7 lagging. Calculate the capacitance required in parallel with the motor to raise the power factor to 0.9 lagging.

69.5 μF
99.5 μF
79.5 μF
89.5 μF

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 1)
A balanced delta connected load of 8+j6 Ω per phase is connected to a 415 V, 50 Hz, 3-phase supply lines. If the input power factor is improved to 0.9 by connecting a star connected capacitor bank, then the required kVAR of the bank is

16.98 kVAR
14.98 kVAR
8.98 kVAR
10.98 kVAR

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 1)
Insulation Power Factor testing on an oil-filled transformer is not helpful in determining ___

Condition of paper insulation (change in watts losses)
Movement of the windings (change in capacitance)
Turns ratio values
Whether the oil test indicates moisture

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP