MGVCL Exam Paper (30-07-2021 Shift 1)
Insulation Power Factor testing on an oil-filled transformer is not helpful in determining ___

Whether the oil test indicates moisture
Turns ratio values
Movement of the windings (change in capacitance)
Condition of paper insulation (change in watts losses)

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 1)
As per ___ guidelines, if the ratio of carbon dioxide (CO₂) and carbon monoxide (CO) in dissolved gas analysis is ___, it is predicted that the condition of paper insulation inside the transformer is poor.

IEC-599, more than 11
IEC-599, less than 11
IEC-899, more than 11
IEC-899, less than 11

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 1)
Determine maximum permissible load which a 15 MVA, ONAN cooled transformer to IS : 2026 can take for 6 hr, if the initial load on it was 12 MVA. The weighted ambient temperature is 20˚C. Assume the permissible load kVA as a fraction of rated kVA is 1.25.

15 MVA
18.75 MVA
9.6 MVA
12 MVA

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 1)
A single phase motor connected to 400 V, 50 Hz supply takes 30 A at a power factor of 0.7 lagging. Calculate the capacitance required in parallel with the motor to raise the power factor to 0.9 lagging.

89.5 μF
79.5 μF
69.5 μF
99.5 μF

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP