There is one IEC guideline, number is IEC 599, Statement of guideline is that "If the ratio of carbon dioxide and Carbon monoxide in Dissolve gas analysis test result is more than 11, it is predict that the condition of paper insulation inside the transformer is poor." For healthy condition this ratio will be between 4 to 11.
Current flow through the circuit, I = V/Z = 400/10 = 41.5 A Power factor = 8/10 = 0.8 After connecting a capacitor bank, the reactive power component of current changes but the active power component of current is unchanged. I1*cosφ1 = I2*cosφ2 41.5*0.8 = I2*0.9 I2 = 36.88 A Q1 (before connecting capacitor) = √3*VL*IL*sinφ1 = √3*415*41.5*sin(36.86) = 26.847 kVAR Q2 (after connecting capacitor) = √3*VL*IL*sinφ2 = √3*415*36.88*sin(25.84) = 15.867 kVAR kVAR supplied by capacitor bank = Q1 - Q2 = 26.847 - 15.867 = 10.98 kVAR
Bus Type - Known Parameter - Unknown Parameter Load Bus -P, Q - V, phase angle Generator Bus - P, V (magnitude) - Q, Voltage phase angle Slack Bus Voltage - magnitude and phase angle - P, Q