Which type of connection is employed for current transformers for the protection of delta- star connected 3-phase transformer?
The connection of CT on primary and secondary side is always reverse to the connection of transformer. To protect the power transformer with star-delta against fault, the type of connection of CTs should be in the delta–star connection otherwise the relay will operate when an external fault occurs due to zero sequence currents
As per the key statistics data of IEA With electricity consumption reached to 1,164 TWh in the country till November 2019, India ranked third among the top ten electricity consuming countries across the globe.
For small turbine starts generating power 12.6 kph (3.5 m/s) is the typical cut-in speed. At 36–54 kph (10–15 m/s) produces maximum generation power. At 90 kph (25 m/s) maximum, the turbine is stopped or braked.
Thermistors are ideal when measuring a single point temperature that is within 50°C of ambient. If the temperatures are excessively high or low, a thermistor will not work. Most thermistors work best in the range between -55°C and +114°C. Sensitivity of thermistor is high. Span value of thermistor is low.