Power Systems
The positive, negative and zero sequence per unit impedance of two generators connected in parallel are X1 = 0.12 pu, X2 = 0.096 pu and X0 = 0.036 pu. For LG fault at generator terminals (with 1 pu voltage) the positive sequence current will be

 8.936 pu
 10.936 pu
 7.936 pu
 9.936 pu

ANSWER DOWNLOAD EXAMIANS APP

Power Systems
The value of off diagonal elements is

 sum of admittances connected at bus j
 which is connected between bus i and bus j with positive sign
 which is connected between bus i and bus j with negative sign
 sum of admittances connected at bus i

ANSWER DOWNLOAD EXAMIANS APP