Power Systems
The neutral of 10 MVA, 11 kV alternator is earthed through a resistance of 5 ohms. The fault ready is set to operate at 0.75 A. The current transformers have a ratio of 1000/5. What is the percentage of the alternator winding is protected?

 15%
 85%
 11.8%
 88.2%

ANSWER DOWNLOAD EXAMIANS APP