The current flowing in to a balanced delta connected load through line 'a' is 10 A when the conductor of line ’b’ is open. With the current in line 'a' as reference, compute the symmetrical components of the line currents. Assume the phase sequence of ’abc’.
The ratio of full load current to short circuit current = 1/6 Xsc = j/(1/6) External reactance required = j*((1/6) - 0.06)) = j*0.106 pu Full load current = (40*1000)/(√3*15) = 1539.6 A Per unit reactance = j*0.106 = (I*Xr)/V j*0.15 = (1539.6*Xb)/((15/√3)*1000)) = 0.60 ohm
The capacity factor is the ratio of an actual electrical energy output over a given period of time to the maximum possible electrical energy output over that period. Nuclear power plants are at the high end of the range of capacity factors
Bus Type - Known Parameter - Unknown Parameter Load Bus -P, Q - V, phase angle Generator Bus - P, V (magnitude) - Q, Voltage phase angle Slack Bus Voltage - magnitude and phase angle - P, Q