The current flowing in to a balanced delta connected load through line 'a' is 10 A when the conductor of line ’b’ is open. With the current in line 'a' as reference, compute the symmetrical components of the line currents. Assume the phase sequence of ’abc’.
Type B MCB: Type B devices are generally suitable for domestic applications. They are designed to trip at fault currents of 3 - 5 times rated current.
Type C MCB: Type C devices are the normal choice for commercial and industrial applications These devices are designed to trip at 5 - 10 times rated current
Type D MCB: The Type D devices have more limited applications, normally in industrial use where high inrush currents may be expected. Type D devices are designed to trip at 10 - 20 times.
The tendency of a Reach of Distance Relay to operate at impedance larger than its setting value is known as overreach. Overreach is the presence of d.c. offset in the fault current wave, as the offset current has a higher peak value than that of a symmetrical wave for which the relay is set.
Bus Type - Known Parameter - Unknown Parameter Load Bus -P, Q - V, phase angle Generator Bus - P, V (magnitude) - Q, Voltage phase angle Slack Bus Voltage - magnitude and phase angle - P, Q