The current flowing in to a balanced delta connected load through line 'a' is 10 A when the conductor of line ’b’ is open. With the current in line 'a' as reference, compute the symmetrical components of the line currents. Assume the phase sequence of ’abc’.

Ia₀ = 0 A.Ia₁ = (-1.66 + j2.88) A.Ia₂ = (1.66 + j2.88) A.
Ia₀ = 10 A.Ia₁ = (-5 + j2.44) A.Ia₂ = (5 - j2.44) A.
Ia₀ = 0 A.Ia₁ = (-5 + j2.88) A.Ia₂ = (5 - j2.88) A.
Ia₀ = 10 A.Ia₁ = (-1.66 + j2.88) A.Ia₂ = (1.66 + j2.88) A.

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 3)
The DC offset in fault current causes conventional over-current (OC) relays to :

under-reach
over-reach
reach remains unaffected due to DC offset
sometimes under-reach and sometimes over-reach

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 3)
Consider the following statements and choose the correct option.
Statement 1: The speed regulation of a synchronous motor is always unity.
Statement 2: In a synchronous motor, at no-load condition, and with normal excitation the armature current drawn by a synchronous motor is in phase with applied voltage.

Statement 1 is FALSE and Statement 2 is TRUE
Both Statement 1 and Statement 2 are TRUE
Statement 1 is TRUE and Statement 2 is FALSE
Both Statement 1 and Statement 2 are FALSE