MGVCL Exam Paper (30-07-2021 Shift 3)
Murray loop test is performed on a faulty cable 300 m long. At balance, the resistance connected to the faulty core was set at 20 Ω and the resistance of the resistor connected to the sound core was 40 Ω. Calculate the distance of the fault point from the test end.
Bus Type - Known Parameter - Unknown Parameter Load Bus -P, Q - V, phase angle Generator Bus - P, V (magnitude) - Q, Voltage phase angle Slack Bus Voltage - magnitude and phase angle - P, Q
The capacity factor is the ratio of an actual electrical energy output over a given period of time to the maximum possible electrical energy output over that period. Nuclear power plants are at the high end of the range of capacity factors
Type B MCB: Type B devices are generally suitable for domestic applications. They are designed to trip at fault currents of 3 - 5 times rated current.
Type C MCB: Type C devices are the normal choice for commercial and industrial applications These devices are designed to trip at 5 - 10 times rated current
Type D MCB: The Type D devices have more limited applications, normally in industrial use where high inrush currents may be expected. Type D devices are designed to trip at 10 - 20 times.