Power Systems The zero sequence current of a generator for line to ground fault is j3 pu. Then the current through the neutral during the fault is j9 pu j1 pu j3 pu j6 pu j9 pu j1 pu j3 pu j6 pu ANSWER DOWNLOAD EXAMIANS APP
Power Systems Which of the following statement is/are true?Zn nether 1 nor 2 The neutral grounding impedance Zn appears as 3Zn in zero sequence equivalent circuit The neutral grounding impedance Zn appears as Zn in zero sequence equivalent circuit both 1 and 2 nether 1 nor 2 The neutral grounding impedance Zn appears as 3Zn in zero sequence equivalent circuit The neutral grounding impedance Zn appears as Zn in zero sequence equivalent circuit both 1 and 2 ANSWER DOWNLOAD EXAMIANS APP
Power Systems A fault occurring at the terminals of an unloaded synchronous generator operating at its rated voltage has resulted in the following values of currents and voltages. IR0 = j 2.37 pu IR1 = -j 3.05 pu IR2 = j 0.68 pu VR0 = VR1 = VR2 = 0.237 pu. Which of the following faults has occurred? LLL LL LLG LG LLL LL LLG LG ANSWER DOWNLOAD EXAMIANS APP
Power Systems The line currents of 3-phase supply are: IR = 3 + j 5 A IY =2 + j 2 A IB = -2 - j 1 A The zero sequence current will be 1 + j 2 A 1 + j 4 A 5 + j 7 A -2 - j 1 A 1 + j 2 A 1 + j 4 A 5 + j 7 A -2 - j 1 A ANSWER DOWNLOAD EXAMIANS APP
Power Systems An unloaded generator with a pre-fault voltage 1 pu has the following sequence impedance: Z0 = j 0.15 pu, Z1 = Z2 = j 0.25 pu The neutral is grounded with a reactance of 0.05 pu. The fault current in pu for single line to ground fault is 7.25 pu 3.75 pu 4.28 pu 2.5 pu 7.25 pu 3.75 pu 4.28 pu 2.5 pu ANSWER DOWNLOAD EXAMIANS APP