A fault occurring at the terminals of an unloaded synchronous generator operating at its rated voltage has resulted in the following values of currents and voltages. IR0 = j 2.37 pu IR1 = -j 3.05 pu IR2 = j 0.68 pu VR0 = VR1 = VR2 = 0.237 pu. Which of the following faults has occurred?

 LLL
 LL
 LG
 LLG

ANSWER DOWNLOAD EXAMIANS APP

Power Systems
Which of the following statement is/are true?Zn

 both 1 and 2
 The neutral grounding impedance Zn appears as 3Zn in zero sequence equivalent circuit
 The neutral grounding impedance Zn appears as Zn in zero sequence equivalent circuit
 nether 1 nor 2