Electrical Machines
If the applied voltage of a certain transformer is increased by 50% and the frequency is reduced by 50%, the maximum flux density will (assuming that the magnetic circuit remains unsaturated)

 remain the same as the original
 changes to three times the original value
 changes to 1.5 times the original value
 changes to 0.5 times the original value

ANSWER DOWNLOAD EXAMIANS APP

Electrical Machines
A dc shunt generator, when driven without any excitation, showed an open circuit voltage of 12 V. When the field winding was excited, the voltage dropped to zero. It happened because

 there was no residual magnetism in the field circuit
 field winding was wrongly connected
 there was a break in the armature circuit
 field resistance was higher than critical resistance

ANSWER DOWNLOAD EXAMIANS APP