Determine the ohmic value of the current limiting reactor per phase external to a 30 MVA, 11 kV, 50 Hz, three phase synchronous generator which can limit the current on short circuit of 5 times the full load current. The reactance of the synchronous generator is 0.05 pu.

0.405 Ω
0.605 Ω
0.305 Ω
0.805 Ω

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 1)
Three equal star-connected inductors take 8 kW at 0.8 power factor when connected to a 460 V three - phase 3-wire supply. If one of the inductor in phase – Y is short circuited, then the line current in phase-Y is ___ Assume RYB sequence.

31.7 A
37.6 A
27.6 A
21.7 A

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 1)
A THHN conductor will have 75°C termination on one end and a 60/75°C termination on the other, which ampacity column will be used?

75°C column
None of these
60°C column
90°C column

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP