A single phase motor connected to 400 V, 50 Hz supply takes 30 A at a power factor of 0.7 lagging. Calculate the capacitance required in parallel with the motor to raise the power factor to 0.9 lagging.

89.5 μF
79.5 μF
99.5 μF
69.5 μF

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 1)
The expression for voltage regulation of a short transmission line for lagging power factor is given by: ___, where, 'I' is the line current, 'V_r' is the receiving end voltage, 'R' is the line resistance and 'X' is the line reactance.

(IX cosφ_r - IR sinφ_r)/V_r
(IX cosφ_r + IR sinφ_r)/V_r
(IR cosφ_r + IX sinφ_r)/V_r
(IR cosφ_r - IX sinφ_r)/V_r

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 1)
Consider the following two statements and choose the correct answer.
Statement 1: The V-curves of a synchronous motor show relationship between armature current and supply voltage.
Statement 2: The plot of power factor against the field current of synchronous motor is known as inverted V curves.

Statement 1 is FALSE and Statement 2 is TRUE
Both Statement 1 and Statement 2 are TRUE
Statement 1 is TRUE and Statement 2 is FALSE
Both Statement 1 and Statement 2 are FALSE

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP