MGVCL Exam Paper (30-07-2021 Shift 1)
A transformer designed for operation at 60 Hz supply is working at 50 Hz supply system without changing its voltage and current ratings. Compared to the full load efficiency at 60 Hz, the full load transformer efficiency at 50 Hz.

remains unaltered
increases marginally
increases by 30%
decreases marginally

ANSWER DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 1)
The current flowing to a balanced delta connected load through line 'a' is 15 A when the conductor of line 'b' is open. With the current in line 'a' as reference, compute the symmetrical components of the line currents. Assume the phase sequence of 'abc'.

Ia₀ = 0 AIa₁ = (-7.5 - j13) AIa₂ = (-7.5 - j4.33) A
Ia₀ = 0 AIa₁ = (7.5 - j13) AIa₂ = (7.5 + j13) A
Ia₀ = 0 AIa₁ = (7.5 + j4.33) AIa₂ = (-7.5 - j4.33) A
Ia₀ = 0 AIa₁ = (7.5 + j4.33) AIa₂ = (7.5 - j 4.33) A

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 1)
Case 1: The PV connected to the DC bus was injecting 20 kW of power constituting of 1 kW of loss
Case 2: The same PV is connected to the AC bus constituting to 1.5 kW loss. Find out the change in efficiency from Case 1 to Case 2?

2.5% increase
2.5% decrease
5% decrease
5% increase

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP