Condition of good conductor: σ/ϵω >> 1 Equation is given by: The constant ratio = σ/ϵω = 44913.6 σ/ϵω >> 1. hence sea water is a acting as a good conductor Since attenuation is 90%, so transmission is 10% So, e^(-αx) = 0.1
Attenuation constant = √(σμϵ/2) = 0.702 -αx = ln(0.1) x = 3.27 m
Bus Type - Known Parameter - Unknown Parameter Load Bus -P, Q - V, phase angle Generator Bus - P, V (magnitude) - Q, Voltage phase angle Slack Bus Voltage - magnitude and phase angle - P, Q
In bias differential protection for transformer, There are two basic settings required to setup the percentage biased differential protection. 1. Minimum pickup 2. The slope.
The minimum pick-up covers the transformer magnetizing current typically 1-4% of transformer rating. A pick up of 0.2 to 0.3 times the TAP is recommended for general cases.
The slope is defined by determining the potential sources of differential current.
For single phase induction motor, P = VIcosφ P = 400*30*0.7 P = 8400 W Q1 = P*tan(φ) = 8400*1.020 Q = 8568.82 VAR Now power factor change to 0.9 So, φ' = 25.84 degree Q = 8400*tan(25.84) Q = 4067.95 Qnet = Q - Q' Qnet = 8568.82 - 4067.95 Qnet = 4500.8 C = V²/(2ᴨf) C = (400*400)/(2ᴨ*50) C = 8.95*10⁻⁵ C = 89.5 μF