The current flowing to a balanced delta connected load through line 'a' is 15 A when the conductor of line 'b' is open. With the current in line 'a' as reference, compute the symmetrical components of the line currents. Assume the phase sequence of 'abc'.

Ia₀ = 0 AIa₁ = (7.5 + j4.33) AIa₂ = (7.5 - j 4.33) A
Ia₀ = 0 AIa₁ = (7.5 + j4.33) AIa₂ = (-7.5 - j4.33) A
Ia₀ = 0 AIa₁ = (-7.5 - j13) AIa₂ = (-7.5 - j4.33) A
Ia₀ = 0 AIa₁ = (7.5 - j13) AIa₂ = (7.5 + j13) A

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 1)
For protection of inter-turn fault in transformer, the relays preferred are

Buchholz's relay and differential relay
Overcurrent relay and differential relay
Overcurrent relay and Buchholz's relay
Buchholz's relay, overcurrent relay and differential relay

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 1)
In a 3-phase, 4-wire, 400/230 V system, a lamp (L1) of 100 W is connected to one phase and neutral and a lamp (L2) of 150 W is connected to the second pahse and neutral. If the neutral wire is disconnected accidently, what will be the voltage across a 100 W lamp (L1)?

120V
240V
180V
160 V