A thermal generating station has an installed capacity of 15 MW and supplies a daily load of 10 MW for 12 hours and 5 MW for remaining 12 hours. If the load factor is 0.8. Find the reserve capacity of the station?

 18 MW
 5 MW
 10 MW
 9 MW

ANSWER DOWNLOAD EXAMIANS APP

Power Systems
In a biased differential relay the bias is defined as the ratio of

  fault current and restraining coil current.
  operating coil current and restraining coil current.
  fault current and operating coil current.
  number of turns of restraining and operating coil.

ANSWER DOWNLOAD EXAMIANS APP

Power Systems
In boiler water reactor (BWR)

 enriched uranium is used as fuel.
 there is danger of radioactive contamination of steam.
  all of above.
 the feed water acts both coolant and a moderator.