Power Systems A power station has a maximum demand of 15000 kW. The annual load factor is 50% and plant capacity factor is 40%. What is the reserve capacity of the plant? 3750 kW 3000 kW 7500 kW 6000 kW 3750 kW 3000 kW 7500 kW 6000 kW ANSWER DOWNLOAD EXAMIANS APP
Power Systems Which of the following method is used for changing power factor from leading to lagging shunt reactor series capacitor shunt capacitor any of the above shunt reactor series capacitor shunt capacitor any of the above ANSWER DOWNLOAD EXAMIANS APP
Power Systems Surge tank is kept very close to the generator turbine spill way pen stock generator turbine spill way pen stock ANSWER DOWNLOAD EXAMIANS APP
Power Systems A loss less transmission line having surge impedance loading (SIL) of 2280 MW is provided with a uniformly distributed series capacitive compensation of 30 %. Then SIL of compensated transmission line will be 3257 MW. 2725 MW. 2280 MW. 1835 MW. 3257 MW. 2725 MW. 2280 MW. 1835 MW. ANSWER DOWNLOAD EXAMIANS APP
Power Systems In a power system with negligible resistance, the fault current at a point is 8.00 pu. The series reactance is to be included at the fault point to limit the short circuit. current to 5.00 pu is 0.075 pu. 0.125 pu. 3.000 pu. 0.200 pu. 0.075 pu. 0.125 pu. 3.000 pu. 0.200 pu. ANSWER DOWNLOAD EXAMIANS APP
Power Systems A 3 - Φ, 33 kV oil circuit breaker is rated 1200 A, 2000 MVA, 3 s. The symmetrical breaking current is 1200 A. 104.8 kA. 3600 A. 35 kA. 1200 A. 104.8 kA. 3600 A. 35 kA. ANSWER DOWNLOAD EXAMIANS APP