MGVCL Exam Paper (30-07-2021 Shift 2)
A generating station having 'n' section busbars each rated at Q kVA with ×% reactance is connected on the tie-bars systems through busbar reactances of b%. Determine the short circuit kVA if a 3-phase fault takes place on one section.

Q[(1/x) + (n+1)/(bn+x)]
Q[(1/x) + (n+1)/(bn-x)]
Q[(1/x) + (n-1)/(bn+x)]
Q[(1/x) - (n+1)/(bn-x)]

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 2)
In transformer, a Sweep Frequency Response Analysis (SFRA) test will help detect ____

Aging by-products
Age of the insulation
Moisture in the windings
Movement / damage to internal components

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 2)
In a single phase energy meter, the shunt electromagnet is energized by a ____of ____

current coil, thick wire of few turns
current coil, thin wire of more turns
pressure coil, thin wire of more turns
pressure coil, thick wire of few turns

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 2)
Consider a solar PV plant with the following specific conditions: Analysis period: 1 year
Measured average solar irradiation intensity in 1 year: 120 kWh/m²
Generator area of the PV plant: 10 m²
Efficiency factor of the PV modules: 15%
Electrical energy actually exported by plant to grid: 110 kWh
Calculate the performance ratio.

0.8111
0.6111
0.7111
0.5111

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 2)
A 3-phase motor load has a p.f. of 0.397 lagging. The two wattmeter method used to measure power show the input as 30 kW. Find the reading on each wattmeter.

W1 = 10 kW and W2 = 20 kW
W1 = -5 kW and W2 = 35 kW
W1 = -10 kW and W2 = 40 kW
W1 = 5 kW and W2 = 25 kW

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP