A generating station having 'n' section busbars each rated at Q kVA with ×% reactance is connected on the tie-bars systems through busbar reactances of b%. Determine the short circuit kVA if a 3-phase fault takes place on one section.

Q[(1/x) - (n+1)/(bn-x)]
Q[(1/x) + (n-1)/(bn+x)]
Q[(1/x) + (n+1)/(bn-x)]
Q[(1/x) + (n+1)/(bn+x)]

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 2)
According to Global Wind Energy Council in 2016, India ranked____ in the Global Wind Power Installed Capacity Index with cumulative installed wind power generation.

Second
Third
First
Fourth

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 2)
The voltage applied to a transformer primary is increased keeping V/f constant. With this, the core loss ____ and the magnetizing current (Im) ____

remains constant, decreases
decreases, increases
increases, remains constant
increases, increases