MGVCL Exam Paper (30-07-2021 Shift 2)
A generating station having 'n' section busbars each rated at Q kVA with ×% reactance is connected on the tie-bars systems through busbar reactances of b%. Determine the short circuit kVA if a 3-phase fault takes place on one section.

Q[(1/x) + (n-1)/(bn+x)]
Q[(1/x) - (n+1)/(bn-x)]
Q[(1/x) + (n+1)/(bn+x)]
Q[(1/x) + (n+1)/(bn-x)]

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 2)
Consider the following statements associated with Buchholz's relays.
Statement 1: Buchholz's relay is a current operated device.
Statement 2 : Buchholz's relay is placed between the transformer tank and the conservator.

Both Statement 1 and Statement 2 are TRUE
Statement 1 is TRUE and Statement 2 is FALSE
Both Statement 1 and Statement 2 are FALSE
Statement 1 is FALSE and Statement 2 is TRUE

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 2)
A three-phase 400 V, 6-pole, 50 Hz squirrel-cage induction motor is running at a slip of 5%. The speed of rotor with respect to stator magnetic field and speed of the stator magnetic field with respect to rotor magnetic field are

-50 rpm, 1000 rpm
950 rpm, zero
-50 rpm, zero
950 rpm, 1000 rpm

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP