MGVCL Exam Paper (30-07-2021 Shift 2)
A delta-connected balanced three-phase load is supplied from a three-phase, 400 V supply. The line current is 20 A and the power taken by the load is 10 kW. Find the power factor.

0.62
0.82
0.52
0.72

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 2)
In a short circuit test on circuit breaker, time to reach the peak re-striking voltage is 50 µs with the peak restriking voltage of 100 kV. Determine average RRRV (Rate of rise re-striking voltage)?

4 x 10⁶ kV/sec
2 x 10⁶ kV/sec
1 x 10⁶ kV/sec
3 x 10⁶ kV/sec

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 2)
The magnitude of the generator earth-fault current is limited by

inserting the stabilizing resistance in series with the relay
inserting suitable resistance in neutral grounding circuit
controlling field exciter
using higher rating CTs

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 2)
Interposing current-transformer (CT) is used in differential protection of a transformer to

match the standard ratio of CTs used on both sides of the transformer winding
increase the sensitivity of the relay
limit the main CT secondary current
minimize the effect of saturation of the main CTs