MGVCL Exam Paper (30-07-2021 Shift 2)
A delta-connected balanced three-phase load is supplied from a three-phase, 400 V supply. The line current is 20 A and the power taken by the load is 10 kW. Find the power factor.

0.82
0.62
0.72
0.52

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 2)
A single phase motor connected to 415 V, 50 Hz supply takes 30 A at a power factor of 0.7 lagging. Calculate the capacitance required in parallel with the motor to raise the power factor to 0.9 lagging.

66.32 µF
76.32 µF
96.32 µF
86.32 µF

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 2)
According to Global Wind Energy Council in 2016, India ranked____ in the Global Wind Power Installed Capacity Index with cumulative installed wind power generation.

Third
Second
Fourth
First

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 2)
The magnitude of the generator earth-fault current is limited by

inserting suitable resistance in neutral grounding circuit
controlling field exciter
inserting the stabilizing resistance in series with the relay
using higher rating CTs

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 2)
In transformer, a Sweep Frequency Response Analysis (SFRA) test will help detect ____

Aging by-products
Age of the insulation
Movement / damage to internal components
Moisture in the windings

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP