A delta-connected balanced three-phase load is supplied from a three-phase, 400 V supply. The line current is 20 A and the power taken by the load is 10 kW. Find the power factor.

0.72
0.62
0.82
0.52

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 2)
A coil having an inductance of 100 mH is magnetically coupled to another coil having an inductance of 900 mH. The coefficient of coupling between the coils is 0.45. Calculate the equivalent inductance if the two coils are connected in series opposing.

932 mH
1135 mH
730 mH
1270 mH

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 2)
In a power network, 400 kV is recorded at a 415 kV bus. A 50 MVAR, 415 kV shunt reactor is connected to the bus. What is the reactive power absorbed by the shunt reactor?

46.45 MVAR
76.45 MVAR
66.45 MVAR
56.45 MVAR

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 2)
Interposing current-transformer (CT) is used in differential protection of a transformer to

match the standard ratio of CTs used on both sides of the transformer winding
increase the sensitivity of the relay
minimize the effect of saturation of the main CTs
limit the main CT secondary current

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP