Power Systems Which of the following power plants can generate power at unpredictable or uncontrollable time Wind turbine. Cooling tower. Condenser. Pulverising unit. Wind turbine. Cooling tower. Condenser. Pulverising unit. ANSWER DOWNLOAD EXAMIANS APP
Power Systems Two insulator discs of identical capacitance value C make up a string for a 22 kV, 50 Hz, single phase overhead line insulation system. If pin to earth capacitance is also C, then find the string efficiency? 50% 86%% 75% 90% 50% 86%% 75% 90% ANSWER DOWNLOAD EXAMIANS APP
Power Systems An unloaded generator with a pre-fault voltage 1 pu has the following sequence impedance: Z0 = j 0.15 pu, Z1 = Z2 = j 0.25 pu The neutral is grounded with a reactance of 0.05 pu. The fault current in pu for single line to ground fault is 7.25 pu 4.28 pu 2.5 pu 3.75 pu 7.25 pu 4.28 pu 2.5 pu 3.75 pu ANSWER DOWNLOAD EXAMIANS APP
Power Systems A 3-phase breaker is rated at 2000 MVA, 33 kV, its making current will be 49 kVA. 35 kVA. 70 kVA. 89.22 kVA. 49 kVA. 35 kVA. 70 kVA. 89.22 kVA. ANSWER DOWNLOAD EXAMIANS APP
Power Systems The load duration curve for a system is 8 hours 30 MW, 16 hours 25 MW and 24 hours 20 MW. The load factor will be 0.25. 0.83. 1.3. 0.44. 0.25. 0.83. 1.3. 0.44. ANSWER DOWNLOAD EXAMIANS APP
Power Systems Which of the following plants has the maximum eapital cost Diesel plants. Steam plants. Nuclear plants. Hydro-plants. Diesel plants. Steam plants. Nuclear plants. Hydro-plants. ANSWER DOWNLOAD EXAMIANS APP