Electrical Machines
Two synchronous generators operating in parallel 200 MW and 400 MW respectively. The drooping characteristics of their governors are identical as 4% from no load to full load. Consider the governors operating at 50Hz on no load. What is the operating frequency, if the load is 600 MW?

 50 Hz
 48 Hz
 48.5 Hz
 45 HZ

ANSWER DOWNLOAD EXAMIANS APP