Two synchronous generators operating in parallel 200 MW and 400 MW respectively. The drooping characteristics of their governors are identical as 4% from no load to full load. Consider the governors operating at 50Hz on no load. What is the operating frequency, if the load is 600 MW?

 48 Hz
 45 HZ
 48.5 Hz
 50 Hz

ANSWER DOWNLOAD EXAMIANS APP

Electrical Machines
The residual magnetism of a self-excited dc generator is lost. To build up its emf again

 the armature connection must be reversed
 the field winding must be replaced
 field winding must be excited by low voltage dc supply
 the field winding connection must be reversed