Electrical Machines
Two synchronous generators operating in parallel 200 MW and 400 MW respectively. The drooping characteristics of their governors are identical as 4% from no load to full load. Consider the governors operating at 50Hz on no load. How will the machine share, if the load is 600 MW?

 230.7 MW and 369.23 MW respectively
 generator 1 gets over load
 generator 2 gets over load
 200 MW and 400MW respectively

ANSWER DOWNLOAD EXAMIANS APP

Electrical Machines
Consider the following statements regarding the magnetization characteristics of a dc generator : 1. It represents the variation of field flux with field current. 2. Variation of open-circuit terminal voltage with field current is independent of speed 3. It is non-linear from zero to rated field current 4. It helps to determine the critical field resistance at a given speed 5. It always starts from the origin Which of these statements are correct ?