Power Systems The rate of rise of re-striking voltage is dependent upon capacitance of the system only inductance of the system only resistance of the system only both 1 and 2 capacitance of the system only inductance of the system only resistance of the system only both 1 and 2 ANSWER DOWNLOAD EXAMIANS APP
Power Systems A 3-phase transmission line has its conductors at the corners of an equilateral triangle with side 3m. The diameter of each conductor is 1.63 cm. The inductance of the line per phase per km is 1.043 mH 1.093 mH 1.182 mH 1.232 mH 1.043 mH 1.093 mH 1.182 mH 1.232 mH ANSWER DOWNLOAD EXAMIANS APP
Power Systems The inertia constant of 100 MVA, 50 Hz, 4 pole generator is 10 MJ/MVA. If the mechanical input to the machine is suddenly raised from 50 MW to 75 MW, the rotor acceleration will be equal to 125 electrical degrees/s² 12.5 electrical degrees/s² 22.5 electrical degrees/s² 225 electrical degrees/s² 125 electrical degrees/s² 12.5 electrical degrees/s² 22.5 electrical degrees/s² 225 electrical degrees/s² ANSWER DOWNLOAD EXAMIANS APP
Power Systems Which of the following effects are associated with transmission line All of these corona effect ferranti effect skin effect All of these corona effect ferranti effect skin effect ANSWER DOWNLOAD EXAMIANS APP
Power Systems The corona loss on a particular system at 60 Hz is 1 kW/km per phase. What is the corona loss at 50 Hz in kW/km per phase? 1.13 0.93 0.882 1 1.13 0.93 0.882 1 ANSWER DOWNLOAD EXAMIANS APP
Power Systems If a generator of 250 MVA rating has an inertia constant of 6 MJ/MVA, its inertia constant on 100 MVA base is 6 MJ/MVA 10.5 MJ/MVA 2.5 MJ/MVA 15 MJ/MVA 6 MJ/MVA 10.5 MJ/MVA 2.5 MJ/MVA 15 MJ/MVA ANSWER DOWNLOAD EXAMIANS APP