Power Systems
The pu parameters for a 500 MVA machine on its own base are: Inertia, H = 20 pu; reactance X = 2 pu. The pu values of inertia and reactance on 100 MVA common base, respectively, are

 100, 10
 4, 0.4
 100, 0.4
 4, 10

ANSWER DOWNLOAD EXAMIANS APP

Power Systems
A lossless power system has to serve a load of 250 MW. There are two generators(G1 and G2) in the system with cost curves C1 and C2 respectively defined as follows: C1 = PG1+0.055P²G1 C2 = 3 PG2 + 0.03 P²G2 Where PG1 and PG2 are the MW injections from generators G1 and G2 respectively. Thus, the minimum cost dispatch will be

 PG1 = 150 MW and PG2 = 100 MW
 PG1 = 100 MW and PG2 = 150 MW
 PG1 = 250 MW and PG2 = 0 MW
 PG1 = 0 MW and PG2 = 250 MW

ANSWER DOWNLOAD EXAMIANS APP