Power Systems Buchholz relay is used for protection of bus bar. none of these. alternator. transformer. bus bar. none of these. alternator. transformer. ANSWER DOWNLOAD EXAMIANS APP
Power Systems A transmission line has a surge impedance of 400 Ω is connected with the cable having surge impedance of 40 Ω, a surge magnitude of 100 kV is travelling from the transmission line towards the cable. Find the reflected voltage? -81.82 kV 18.18 kV -18.18 kV 81.82 kV -81.82 kV 18.18 kV -18.18 kV 81.82 kV ANSWER DOWNLOAD EXAMIANS APP
Power Systems The inertia constant of 100 MVA, 50 Hz, 4 pole generator is 10 MJ/MVA. If the mechanical input to the machine is suddenly raised from 50 MW to 75 MW, the rotor acceleration will be equal to 22.5 electrical degrees/s² 125 electrical degrees/s² 12.5 electrical degrees/s² 225 electrical degrees/s² 22.5 electrical degrees/s² 125 electrical degrees/s² 12.5 electrical degrees/s² 225 electrical degrees/s² ANSWER DOWNLOAD EXAMIANS APP
Power Systems The neutral of 10 MVA, 11 kV alternator is earthed through a resistance of 5 ohms. The fault ready is set to operate at 0.75 A. The current transformers have a ratio of 1000/5. What is the percentage of the alternator winding is protected? 88.2% 85% 15% 11.8% 88.2% 85% 15% 11.8% ANSWER DOWNLOAD EXAMIANS APP
Power Systems For a 500 Hz frequency excitation, a 100 km long power line will be modelled as long transmission line medium transmission line shunt capacitor any of the above long transmission line medium transmission line shunt capacitor any of the above ANSWER DOWNLOAD EXAMIANS APP
Power Systems If all the sequence voltages at the fault point in a power system are equal, then the fault point is a LL LG LLG LLL LL LG LLG LLL ANSWER DOWNLOAD EXAMIANS APP