Building Construction
Raft foundations are used for:

All listed here
Providing increased area of foundation over poor bearing capacity of soil
Counter acting the hydrostatic effect
Spanning over small soft or loose pockets

ANSWER DOWNLOAD EXAMIANS APP

Building Construction
Two columns 50 cm × 50 cm and 60 cm × 60 cm carry 80 tonnes and 120 tonnes of loads respectively. The centre to centre distance between columns is 5.00 metres. The permissible bearing capacity of the soil is 20 t/m2. If the footing is not to project more than 25 cm beyond the outside of the smaller column, pick up the correct design parameters of the footing from the following:

All listed here
The length of the foundation slab = 7.00 m
Distance of
G. of the loads from the smaller column = 3.00 m
Area of footing slab = 11.00 m2

ANSWER DOWNLOAD EXAMIANS APP