The expression for voltage regulation of a short transmission line for leading power factor is given by: ____, where, 'I' is the line current, 'V_r' is the receiving end voltage, 'R' is the line resitance and 'X' is the line reactance.
For lagging power factor = (IR*cosφ + IXsinφ)/V_r For leading power factor = (IR*cosφ - IXsinφ)/V_r Zero voltage regulation occurs on leading power factor only.
Buchholz relay is gas operated relay. It will operate when internal fault occurs in transformer. It is placed between tank to main conservator. It has two contacts trip and alarm. Use of Buchholz relay in distribution transformer is not economical.