The expression for voltage regulation of a short transmission line for leading power factor is given by: ____, where, 'I' is the line current, 'V_r' is the receiving end voltage, 'R' is the line resitance and 'X' is the line reactance.
For lagging power factor = (IR*cosφ + IXsinφ)/V_r For leading power factor = (IR*cosφ - IXsinφ)/V_r Zero voltage regulation occurs on leading power factor only.
The neutral point of a generator is usually earthed to facilitate protection of the stator winding and associated system. Earthing also prevents damaging transient overvoltages in the event of an arcing earth fault or ferro resonance. For HV generators, impedance is usually inserted in the stator earthing connection to limit the magnitude of earth fault current.
The capacity of reactor = 50 MVAr when it is operated at 415 kV. Impedance of reactor = V2/MVAr = (415*415)2/50 = 3444.5 Ω For 400 kV, Reactive power observed = (400*400)/3444.5 = 46.45 MVAR
Or
VAr capacity of capacitor or reactor is proportional to V²
When different types of consumers are charged at different uniform per unit rates, it is said to be Flat Rate Tariff. In this type, the consumers are grouped into different classes. Each class is charged at different uniform rate.