The expression for voltage regulation of a short transmission line for leading power factor is given by: ____, where, 'I' is the line current, 'V_r' is the receiving end voltage, 'R' is the line resitance and 'X' is the line reactance.
For lagging power factor = (IR*cosφ + IXsinφ)/V_r For leading power factor = (IR*cosφ - IXsinφ)/V_r Zero voltage regulation occurs on leading power factor only.
Frequency response analysis is the technique whereby a sinusoidal test signal is used to measure points on the frequency response of a transfer function or impedance function. Sweep Frequency Response Analysis (SFRA) testing provides insight into the mechanical and electrical integrity of transformers.
Main Purpose of SFRA Test: Transformer Core displacement Winding displacement for both rotor and transformer Broken or loosen clamp connections Inter turn short circuit Internal short circuit Winding to Core Earth fault Winding Open circuit condition
The capacity of reactor = 50 MVAr when it is operated at 415 kV. Impedance of reactor = V2/MVAr = (415*415)2/50 = 3444.5 Ω For 400 kV, Reactive power observed = (400*400)/3444.5 = 46.45 MVAR
Or
VAr capacity of capacitor or reactor is proportional to V²
Buchholz relay is gas operated relay. It will operate when internal fault occurs in transformer. It is placed between tank to main conservator. It has two contacts trip and alarm. Use of Buchholz relay in distribution transformer is not economical.