Electrical Machines
Two synchronous generators operating in parallel 200 MW and 400 MW respectively. The drooping characteristics of their governors are identical as 4% from no load to full load. Consider the governors operating at 50Hz on no load. How will the machine share, if the load is 600 MW?

 200 MW and 400MW respectively
 generator 2 gets over load
 230.7 MW and 369.23 MW respectively
 generator 1 gets over load

ANSWER DOWNLOAD EXAMIANS APP

Electrical Machines
A dc shunt generator, when commissioned after a major repair of the field system, failed to build Up voltage. It was because

 field system lost residual magnetism
 field resistance was higher than critical resistance
 field winding was wrongly connected
 there was a break in the armature circuit