The connection of CT on primary and secondary side is always reverse to the connection of transformer. To protect the power transformer with star-delta against fault, the type of connection of CTs should be in the delta–star connection otherwise the relay will operate when an external fault occurs due to zero sequence currents
Bus Type - Known Parameter - Unknown Parameter Load Bus -P, Q - V, phase angle Generator Bus - P, V (magnitude) - Q, Voltage phase angle Slack Bus Voltage - magnitude and phase angle - P, Q
Class B trip curve: The MCB with class B trip characteristics trips instantaneously when the current flowing through it reaches between 3 to 5 times rated current. These MCBs are suitable for cable protection. Hence, For 16 A current Type B MCB disconnect fault at 3*16 = 48 A to 5*16 = 80 A.
The series electromagnet is energized by a coil known as current coil which is connected in series with the load so that it carry the load current. The flux produced by this magnet is proportional to and in phase with the load current.