In a 3-phase, 4-wire, 400/230 V system, a lamp (L1) of 100 W is connected to one phase and neutral and a lamp (L2) of 150 W is connected to the second pahse and neutral. If the neutral wire is disconnected accidently, what will be the voltage across a 100 W lamp (L1)?

240V
120V
160 V
180V

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 1)
A 16 A, Type B Miniature Circuit Breaker (MCB) will disconnect a fault in 0.1s when the fault current is

greater than 32 A
less than 16 A
less than 16 A
between 48 A and 80 A

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 1)
Consider the following statements and choose the correct option:
Statement 1: The magnitude of earth fault current for a given fault position within a winding depends upon the method of neutral grounding.
Statement 2: Earth fault protection for an electric motor is provided by means of instantaneous overcurrent relay.

Both Statement 1 and Statement 2 are TRUE
Statement 1 is FALSE and Statement 2 is TRUE
Statement 1 is TRUE and Statement 2 is FALSE
Both Statement 1 and Statement 2 are FALSE

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 1)
A balanced delta connected load of 8+j6 Ω per phase is connected to a 415 V, 50 Hz, 3-phase supply lines. If the input power factor is improved to 0.9 by connecting a star connected capacitor bank, then the required kVAR of the bank is

8.98 kVAR
14.98 kVAR
10.98 kVAR
16.98 kVAR

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 1)
For protection of inter-turn fault in transformer, the relays preferred are

Overcurrent relay and differential relay
Overcurrent relay and Buchholz's relay
Buchholz's relay and differential relay
Buchholz's relay, overcurrent relay and differential relay

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP