A coil having an inductance of 100 mH is magnetically coupled to another coil having an inductance of 900 mH. The coefficient of coupling between the coils is 0.45. Calculate the equivalent inductance if the two coils are connected in series aiding.
The second generation of smart meters are known as SMETS 2. Full form of SMET is Smart Metering Equipment Technical Specifications. It is with the previous generation known as SMETS 1. SMETS 2 smart meters were introduced in 2018.
Symmetrical breaking current: It is the rms value of a a.c component of the current in the pole at the instant of contact separation.
Asymmetrical breaking current: It is the rms value of the total current comprising the a.c and d.c components of the current in the pole at the instant of contact separation.
In DC microgrid system, Efficiency α 1/Pin For 1 kW loss injecting power is 20 kW For 1.5 kW loss injecting power will be proportional to 30 kW So, Efficiency will be reduced 0.025
The magnitude of earth fault current for a given fault position within a winding demands upon the winding connections and method of neutral grounding. Earth fault protection for an electric motor is provide by instantaneous relay having a setting of approximately 30% of motor rated current in the residual circuits of two CTs and with ground wire.