A lossless power system has to serve a load of 250 MW. There are two generators(G1 and G2) in the system with cost curves C1 and C2 respectively defined as follows: C1 = PG1+0.055P²G1 C2 = 3 PG2 + 0.03 P²G2 Where PG1 and PG2 are the MW injections from generators G1 and G2 respectively. Thus, the minimum cost dispatch will be

 PG1 = 150 MW and PG2 = 100 MW
 PG1 = 0 MW and PG2 = 250 MW
 PG1 = 100 MW and PG2 = 150 MW
 PG1 = 250 MW and PG2 = 0 MW

ANSWER DOWNLOAD EXAMIANS APP

Power Systems
Consider a three phase, 50 Hz, 11 kV distribution system. Each of the conductors is suspended by an insulator string having two identical porcelain insulators. The self capacitance of the insulators is 5 times the shunt capacitance between the link and ground. Find the voltage across the two insulators V1 and V2? (V1 = Voltage of disc nearest to the conductor)

 V1 = 5 kV and V2 = 6 kV
 V1 = 3.46 kV and V2 = 2.89 kV
 V1 = 6 kV and V2 = 5 kV
 V1 = 2.89 kV and V2 = 3.46 kV