Power Systems
An isolated synchronous generator with transient reactance equal to 0.1 pu on a 100 MVA base is connected to the high voltage bus through a step up transformer of reactance 0.1 pu on a 100 MVA base. The fault level at the bus is

 500 MVA
 100 MVA
 200 MVA
 400 MVA

ANSWER DOWNLOAD EXAMIANS APP

Power Systems
In a biased differential relay the bias is defined as the ratio of

  fault current and restraining coil current.
  number of turns of restraining and operating coil.
  fault current and operating coil current.
  operating coil current and restraining coil current.

ANSWER DOWNLOAD EXAMIANS APP