Power Systems For n bus power system size of Y bus matrix is (n-2)×(n-2) (n-1)×(n-1) n×n (n-1)×(n-2) (n-2)×(n-2) (n-1)×(n-1) n×n (n-1)×(n-2) ANSWER DOWNLOAD EXAMIANS APP
Power Systems String chart is drawn between both 1 and 2 nether 1 nor 2 temperature (T) on X- axis, sag(S) and tension (T) on Y-axis T on Y-axis and S and T on on X-axis both 1 and 2 nether 1 nor 2 temperature (T) on X- axis, sag(S) and tension (T) on Y-axis T on Y-axis and S and T on on X-axis ANSWER DOWNLOAD EXAMIANS APP
Power Systems The angular moment of 10 MVA generator is 0.2. Find the new value of angular moment for 20 MVA base? 0.25 pu 0.4 pu 0.2 pu 0.1 pu 0.25 pu 0.4 pu 0.2 pu 0.1 pu ANSWER DOWNLOAD EXAMIANS APP
Power Systems The zero sequence current of a generator for line to ground fault is j3 pu. Then the current through the neutral during the fault is j6 pu j1 pu j9 pu j3 pu j6 pu j1 pu j9 pu j3 pu ANSWER DOWNLOAD EXAMIANS APP
Power Systems If the percentage reactance of an element is 20 % and the full load current is 50 Amp, the short circuit current will be 300 Amp. 250 Amp. 350 Amp. 200 Amp. 300 Amp. 250 Amp. 350 Amp. 200 Amp. ANSWER DOWNLOAD EXAMIANS APP
Power Systems Which of the following plants has the maximum eapital cost Steam plants. Diesel plants. Nuclear plants. Hydro-plants. Steam plants. Diesel plants. Nuclear plants. Hydro-plants. ANSWER DOWNLOAD EXAMIANS APP