Electrical Machines
Two generators operating in parallel with rating 50MW and 100MW respectively. Both their respective governor settings are identical as 4%, consider same no load frequency. How will the machine share a common load of 100 MW

 50 MW and 50 MW respectively
 33.33 MW and 66.67 MW respectively
 any of the above
 66.67 MW and 33.33 MW respectively

ANSWER DOWNLOAD EXAMIANS APP

Electrical Machines
Two synchronous generators operating in parallel 200 MW and 400 MW respectively. The drooping characteristics of their governors are 4% and 5% from no load to full load. Consider the governors operating at 50Hz on no load. How will the machine share, if the load is 600 MW?

 generator 1 gets over load
 generator 2 gets over load
None of these
 200 MW and 400MW

ANSWER DOWNLOAD EXAMIANS APP

Electrical Machines
Two synchronous generators operating in parallel 200 MW and 400 MW respectively. The drooping characteristics of their governors are identical as 4% from no load to full load. Consider the governors operating at 50Hz on no load. How will the machine share, if the load is 600 MW?

 generator 1 gets over load
 200 MW and 400MW respectively
 generator 2 gets over load
 230.7 MW and 369.23 MW respectively

ANSWER DOWNLOAD EXAMIANS APP