Electrical Machines
Two synchronous generators operating in parallel 200 MW and 400 MW respectively. The drooping characteristics of their governors are 4% and 5% from no load to full load. Consider the governors operating at 50Hz on no load. How will the machine share, if the load is 600 MW?

 200 MW and 400MW
 generator 2 gets over load
 generator 1 gets over load
None of these

ANSWER DOWNLOAD EXAMIANS APP

Electrical Machines
Torque angle of a synchorous machine operating from a constant voltage bus is usually defined as the space angle between

 Rotor mmf wave and resultant flux density wave.
 Stator mmf wave and resultant mmf wave.
  Rotor mmf wave and stator mmf wave.
 Stator mmf wave and resultant flux density.

ANSWER DOWNLOAD EXAMIANS APP

Electrical Machines
In a dc generator operating on load with its brushes on the geometrical neutral axis (GNA), the magnetic neutral axis (MNA) is shifted in the direction of rotation. Now, if the brushes are given a lead of 90° (electrical), then the MNA will

 shift forward by 90°
 shift forward by less than 90°
 coincide with the GNA
 shift forward by more than 90°