Electrical Machines
Two synchronous generators operating in parallel 200 MW and 400 MW respectively. The drooping characteristics of their governors are 4% and 5% from no load to full load. Consider the governors operating at 50Hz on no load. How will the machine share, if the load is 600 MW?

 generator 1 gets over load
 generator 2 gets over load
 200 MW and 400MW
None of these

ANSWER DOWNLOAD EXAMIANS APP

Electrical Machines
Which of the following factors improve commutation in a dc machine ? 1. High contact resistance of brushes 2. High inductance of the coils undergoing commutation 3. Shifting of brushes in the direction of rotation for a generator and in the opposite direction For a motor 4. Narrow width for the commutation bars Select the correct answer using the codes given below : Codes :

 1 and 3
 1, 2, and 3
 1, 2 and 4
 2, 3 and 4

ANSWER DOWNLOAD EXAMIANS APP