Electrical Machines
The results of a slip test for determining direct axis (Xd) and quadrature axis (Xq) reactances of a star connected salient pole alternator are given below Phase values: Vmax = 108 V ; Vmin = 96 V Imax = 12 A ; Imin = 10 A Hence the two reactances will be

 Xd = 9.6Ω and Xq = 9Ω
 Xd = 8Ω and Xq = 10.8Ω
 Xd = 10.8Ω and Xq = 8Ω
 Xd = 9Ω and Xq = 9.6Ω

ANSWER DOWNLOAD EXAMIANS APP

Electrical Machines
Two synchronous generators operating in parallel 200 MW and 400 MW respectively. The drooping characteristics of their governors are identical as 4% from no load to full load. Consider the governors operating at 50Hz on no load. How will the machine share, if the load is 600 MW?

 200 MW and 400MW respectively
 generator 2 gets over load
 230.7 MW and 369.23 MW respectively
 generator 1 gets over load

ANSWER DOWNLOAD EXAMIANS APP