MGVCL Exam Paper (30-07-2021 Shift 2)
A power factor less than unity results in which of the following disadvantages?
(i) Large kVA rating of equipment
(ii)Poor voltage regulation
(iii) Greater conductor size

(i) and (ii) only
(ii) and (iii) only
(i) and (iii) only
(i), (ii) and (iii)

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 2)
Which of the following does the term 'feeder automation' include?

feeder remote point voltage control
All of these
automatic reclosing
substation reactive power control

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 2)
A generating station having 'n' section busbars each rated at Q kVA with ×% reactance is connected on the tie-bars systems through busbar reactances of b%. Determine the short circuit kVA if a 3-phase fault takes place on one section.

Q[(1/x) + (n-1)/(bn+x)]
Q[(1/x) + (n+1)/(bn-x)]
Q[(1/x) + (n+1)/(bn+x)]
Q[(1/x) - (n+1)/(bn-x)]

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP

MGVCL Exam Paper (30-07-2021 Shift 2)
The necessary equation to be solved during the load flow analysis using Fast-Decoupled method is given below:
where B' and B'' are formed using the imaginary part of the bus admittance matrix, Ybus. If the system consists of 6 buses of which one of the bus is slack bus and 2 bues are voltage regulated buses, then then the matrix B' is of order ____and the matrix B'' is of order____, respectivity.
∆P/|Vi| = - B'∆δ
∆Q/|Vi| = - B''∆|V|

3 and 6
3 and 5
6 and 3
5 and 3

ANSWER EXPLANATION DOWNLOAD EXAMIANS APP